APPLICATIONS:
Control and Signals For control circuits unenclosed, enclosed, direct burial.
Direct Burial Steel armour provides mechanical protection, allowing for the cable to withstand higher stresses, be buried directly and used in external or underground projects.
Outdoor Use Suitable for outdoor use and wet locations where mechanical protection is required.
Armour For Earthing The armouring is normally connected to Earth and can be used as the circuit protective conductor (Earth wire).
Hazardous Areas With correct explosion proof glands this cable can be installed in locations subject to explosion hazards AS/NZS 60079.14.
PRODUCT FEATURES:
- Suitable for circuits buried direct
- Steel wire armoured
- UV stabilised
- Flame retardant
- Metre marking for better length control
- Heat, oil and chemical resistant (see Chemical Rating Chart)
CONSTRUCTION:
Conductor Annealed plain copper stranded (Class 2).
Insulation V-90.
Bedding Sheath SPVC 5V-90.
Armoured Galvanised steel wire armoured.
Outer Sheath SPVC.
CHARACTERISTICS:
Operating Temperature Range Fixed -20°C to 90°C.
Maximum Conductor Temperature 90°C. (Current ratings are based on 30°C air temp. See technical section for de-rating factors).
Rated Voltage 0.6/1kV.
Minimum Bending Radius Fixed 12 x cable diameter.
Sheath Colour Black.
Standard Core Colour Multicore - White (numbered).
Relevant Standards AS/NZS 1125, AS/NZS 3008, AS/NZS 3808, AS/NZS 5000.1, IEC 60332-1-2, AS/NZS 60079.14 ROHS Compliant.