CURRENT CARRYING COMPARISON (AT 30°C AIR AMBIENT TEMPERATURE – PROTECTED FROM THE SUN)

FEATURES: If you can drop down one or two sizes of cable to carry the same current then you also drop down lug sizes, cable diameter and bending radius.

NOTE: For a more detailed and complete range of current carrying capacity, please refer to AS/NZS 3008.1.2.2010 tables 7, 8 & 9. The below current carrying capacities of three single core 0.6/1 KV cables used as fixed wiring which are not subject to flexing in normal use. Cables may be operated in that current range when not exposed to mechanical damage.

    AFX / ML / SF / WC
AHVCY / RSCY SERIES
BFX / BFX-H
AHV SERIES
CONDUCTOR SIZE
mm2
PVC V 90°
INSULATED CABLES
UNENCLOSED TOUCHING
RUBBER R90°
INSULATED CABLES
UNENCLOSED TOUCHING
RUBBER R110°
INSULATED CABLES
UNENCLOSED TOUCHING
6 43 AMPS 51 AMPS 61 AMPS
10 62 AMPS 70 AMPS 86 AMPS
16 81 AMPS 94 AMPS 112 AMPS
25 107 AMPS 125 AMPS 149 AMPS
35 133 AMPS 155 AMPS 184 AMPS
50 168 AMPS 196 AMPS 232 AMPS
70 211 AMPS 248 AMPS 292 AMPS
95 254 AMPS 298 AMPS 352 AMPS
120 301 AMPS 354 AMPS 417 AMPS
APPROX. DE-RATING
FOR DIFFERENT
AMBIENT TEMP.
°C 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
Factor 1.15 1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.65 0.58 0.50 0.41 0.29

 